  • ZY-DGA500油色谱.jpg

ZY-DGA500 oil chromatography, ZY-TX iron core ground current online monitoring system

ZY-DGA500 oil chromatography on-line monitoring device is our company's latest on-line monitoring system for gas and micro-water content in oil, and can integrate on-line monitoring system of iron core ground current according to customer requirements, and intelligent components that meet the national IEC61850 communication protocol. The monitoring device is connected to the transformer body only through the oil inlet and outlet ports, and is easy to install. It adopts the oil circulation working method, no pollution, no fuel consumption, and accurate sampling. The shortest monitoring period can be set to 1 hour, and the maximum detection period can be set arbitrarily. The software system is powerful and easy to operate. It can query real-time data, real-time maps, historical data, trend charts, etc.

Category:

ZY-DGA500 oil chromatography, ZY-TX iron core grounding current online monitoring system

Keywords: online monitoring system | partial discharge detection


Product Description

  ZY-DGA500 oil chromatography on-line monitoring device is our company's latest on-line monitoring system for gas and micro-water content in oil, and can integrate on-line monitoring system of iron core ground current according to customer requirements, and intelligent components that meet the national IEC61850 communication protocol. The monitoring device is connected to the transformer body only through the oil inlet and outlet ports, and is easy to install. It adopts the oil circulation working method, no pollution, no fuel consumption, and accurate sampling. The shortest monitoring period can be set to 1 hour, and the maximum detection period can be set arbitrarily. The software system is powerful and easy to operate. It can query real-time data, real-time maps, historical data, trend charts, etc.

Detection parameters

Minimum detection limit UL / L

Maximum detection limit UL / L

Measurement error

Hydrogen H2

2

2000

The measurement error is less than the minimum detection limit or +/- 30%, and the limit error takes the maximum of both.

C2H2 acetylene

0.5

1000

CH4 methane

0.5

1000

C2H6 ethane

0.5

1000

C2H4 ethylene

0.5

1000

Carbon monoxide

25

5000

Carbon dioxide

25

15000

Micro water value

0

100%

 
  The "DL / T 572 Power Transformer Operating Regulations" requires that the current in the transformer core grounding wire cannot exceed 100MA. The ZY-TX core grounding online monitoring system can monitor the transformer core grounding current value 24/7, and can also When the current in the ground line is found to be greater than 100mA, a current limiting resistor is required to limit the current in the ground line to less than 100mA.
 
  System parameters:
  Working voltage: AC220V, -15% ~ + 15%; power frequency: 50Hz ± 0.5Hz.
  Ground current alarm value: 100mA, automatic alarm when the value is exceeded
  Alarm node capacity: 5A250VAC.
  Measuring current range: 10mA ~ 10A.
  Measurement accuracy: ± 3%
  Ambient temperature: -40 ℃ ~ + 70 ℃.
  Ambient humidity: ≤85%

+

Intelligent detection is a major issue for the planning and construction of the ubiquitous electric power Internet of Things system by the State Grid Corporation of China. It is also a key application for solving the problem of interconnection and data sharing of the operation inspection system. It is also an important basis for the practical application of big data analysis for equipment inspection.


+

A transformer is a device that uses the principle of electromagnetic induction to change AC voltage. The main components are a primary coil, a secondary coil, and an iron core (magnetic core). The main functions are: voltage conversion, current conversion, impedance conversion, isolation, voltage stabilization (magnetic saturation transformer), etc. It is a key device in the power system. Generally, transformers rarely fail. Once a certain defect occurs inside the transformer equipment, equipment failure is extremely easy to occur. Therefore, strengthening and improving the operation monitoring of transformer equipment is of great significance for ensuring the safe operation of transformers.


+

DXK-ZY high-voltage charged display is a new type of device to prevent electrical misoperation. It is an inductive (non-contact) high-voltage charged detection device. The device has advanced design, reasonable structure, complete functions, safety and reliability. It has functions such as flashing display, audible alarm, fault self-test and activation of forced blocking circuit, etc., and has high sensitivity and reliability. This device is suitable for outdoor (also suitable for indoor) electrical network or equipment with AC 50Hz and rated voltage of 40.5 ~ 1100kV, and it is used to reflect the charged condition and prevent electrical misoperation. The device is installed on the line grounding knife switch, the bus grounding knife switch and the busbar pressure change grounding knife switch


ONLINE MESSAGE